ORDINANCE NO. ______     

 

AN ORDINANCE ADOPTING FIRE PREVENTION CODE

FOR THE HUNTLEY FIRE PROTECTION DISTRICT

Huntley, Illinois

 

            WHEREAS, the Huntley Fire Protection District is a fire protection district duly organized under the laws of the State of Illinois; and

            WHEREAS, the Board of Trustees of the District has express power pursuant to 70 ILCS 705/11, to adopt and enforce fire prevention codes and standards parallel to national standards to promote fire prevention; and

            WHEREAS, the Board of Trustees of the District also has full power pursuant to 70 ILCS 705/6, to pass all necessary ordinances, and rules and regulations for the proper management and conduct of the business of the Board of Trustees of the District for carrying into effect the objects for which the District was formed; and

            WHEREAS, the Fire Protection District Act, 70 ILCS 705/11, (the “Act”) empowers and makes it the legal duty and obligation of this Board of Trustees to provide as nearly adequate protection from fire for all persons and property within the District as possible and to prescribe necessary regulations for the prevention and control of fire therein; and    

            WHEREAS, the District is empowered by the Act to provide reasonable safeguards through Fire Prevention Codes to protect the Public Health and Safety against the hazards of fire in buildings and structures; and

            WHEREAS, the Board of Trustees of the District deem it in the best interest of the District to amend and adopt a new Fire Prevention Code using the 2003 Edition of the International Fire Code as the District’s model for the control of fire protection in buildings and structures as herein provided; and each and all of the regulations, provisions, penalties, conditions and terms as amended by the Fire Prevention Codes listed in Exhibit A hereto, are hereby adopted and made a part thereof, as if fully set out in this Ordinance, except for the additions, insertions, deletions and changes set forth in Exhibit A to this Ordinance; and  

            WHEREAS, the 2003 Edition of the ICC International Fire Code is a comprehensive compilation of codes designed to meet the needs of the local fire jurisdictions through model code regulations that prescribe safeguards for the safety and public health of all communities; and

            WHEREAS, the ICC (International Code Council) is a result of the consolidation of three previously recognized model code organizations: BOCA (Building Officials & Code Administrators), ICBO (International Conference of Building Officials) and SBCCI (Southern Building Code Congress International; and

            NOW, THEREFORE, be it ordained by the Board of Trustees of the Huntley Fire Protection District, McHenry & Kane County, Illinois, as follows:

            SECTION 1:   The facts and statements contained in the preamble to this Ordinance are hereby found by the Board of Trustees to be true and correct and are hereby adopted as part of this Ordinance.

            SECTION 2:   The fire prevention code of the Huntley Fire Protection District (hereinafter referred to as the "Fire Prevention Code") shall hereafter be identical with the provisions of the publication(s) listed in Exhibit A hereto, and said publication(s) listed in Exhibit A hereto are hereby incorporated herein by reference as if fully set forth, except as amended in Exhibit A to this Ordinance.  At least three (3) copies of this Fire Prevention Code shall be placed on file with the District and shall be available for public inspection at all times during regular business hours as provided by law.

            SECTION 3:  That it shall be unlawful to design, construct, alter, enlarge, repair, demolish, remove, use or maintain any building or structure within the boundaries of the Huntley Fire Protection District in violation of any terms or provisions of this Ordinance.

            SECTION 4:  That the specific terms and conditions of this Ordinance shall prevail against other existing ordinances of the District to the extent that there might be any conflict.

            SECTION 5:  All persons in violation of the Fire Prevention Code shall be subjected to fines as set forth and established in the Codes and in the District’s Ordinance No. __________.

            SECTION 6:  Future versions of the District’s Fire Prevention Code shall be revised by Board approval of additional Exhibits hereto that amend the current Exhibit A.  All such revisions shall be dated and shall be effective upon approval by the Board of Trustees.

            SECTION 7:  The Board of Trustees of the District hereby declares that should any section, paragraph, sentence or word of this Ordinance or of the Code hereby adopted be declared for any reason to be invalid, it is the intent of said Board of Trustees that it would have passed all other portions of this Ordinance independent of the elimination here from of such portion as may be declared invalid.

            SECTION 8:   Neither the enactment of this Ordinance nor the repeal of any ordinance or parts of ordinances as provided for herein shall be construed to affect or abate any action or cause of action for violation of said prior ordinance or ordinances.

            SECTION 9:   That this Ordinance shall be in full force and effect from and after its passage, approval and publication in accordance with the law.

           

            ADOPTED this            day of _________________, 2004, by the following roll call vote:

            AYES:                                                                                                                                                

            NAYS:                                                                                                                                      

            ABSENT:                                                                                                                                                                                                                                                                                                                                                                                                                                                                                                       

 

                                                                                                                                                                                                                                                            President, Board of Trustees

                                                                                    Huntley Fire Protection District

 

 

 

ATTEST:

 

 

 

 ___________________________________                                                

Secretary, Board of Trustees

Huntley Fire Protection District

 

 

 

 

 

 

 

 

 

 

STATE OF ILLINOIS                       )

                                                )           SS

Counties of McHenry / Kane            )

 

 

                                                                                              SECRETARY’S CERTIFICATE

 

 

            I, BONNIE BAYSER, the duly qualified and acting Secretary of the Board of Trustees of the Huntley Fire Protection District, McHenry & Kane County, Illinois, do hereby certify that I am the keeper of its books and records and that the attached hereto is a true and correct copy of an Ordinance entitled:

ORDINANCE NO.  _________              

 

                                                                                 AN ORDINANCE ADOPTING FIRE PREVENTION CODES

FOR THE HUNTLEY FIRE PROTECTION DISTRICT

 

which Ordinance was duly adopted by said Board of Trustees at a regular meeting held on the  

             Day of _________________, 2004.

            I do further certify that a quorum of said Board of Trustees was present at said meeting and that the Board complied with all requirements of the Illinois Open Meetings Act.

            IN WITNESS WHEREOF, I have hereunto set my hand this                             day of

________________, 2004.

 

                                                                                                                                                                                                                                                Bonnie Bayser, Secretary

                                                                                    Huntley Fire Protection District

                                                                                   

                                                                                   

 


EXHIBIT A

 

HUNTLEY FIRE PROTECTION DISTRICT    (Draft 7/20/04)

FIRE PREVENTION CODE

 

2003 EDITION OF THE INTERNATIONAL FIRE CODE WITH CERTAIN AMENDMENTS

 

 

ADOPTION OF THE INTERNATIONAL FIRE CODE 2003 EDITION

 

The regulations of the 2003 edition of the International Fire Code, as published by the International Code Council is hereby adopted as the regulations governing the safeguard of life and property from the hazards of fire and explosion arising from the storage, handling and use of hazardous substances, materials and devices; and from conditions hazardous to life or property in the use or occupancy of existing or proposed new buildings or premises in the Huntley Fire Protection District with such amendments as are hereafter set forth.

 

 

CHAPTER 1 - ADMINISTRATION

 

 

SECTION 101 – GENERAL

 

101.1 Title

Delete this section and insert the following:

 

These regulations shall be known as the Fire Code of the Huntley Fire Protection District, hereafter referred to as “this Code”.            

 

101.2.1 Appendices

Add as additional

 

Appendices E, F, and G are adopted in entirety.

Appendix B is adopted as referenced in section 508.3.1.

Appendix D is adopted with exceptions noted in Section 503.   

 

102.2

Add as additional

 

3.  Buildings that have been vacated for 90 days or more with the exception of single and two-family residences.

 

 

 

SECTION 103 – DEPARTMENT OF FIRE PREVENTION

 

103.1 General

Delete this section and insert the following:

 

A Fire Prevention Bureau is hereby established within the Huntley Fire Protection District under the direction of the Fire Marshal. The function of the Fire Prevention Bureau shall include, but not be limited to the implementation, administration and enforcement of the provisions of this Code along with other duties deemed necessary by the Chief in the interest of Public Safety.

 

103.2 Appointment

Delete this section and insert the following:

 

The Chief of the Huntley Fire Protection District, by reason of said position, shall appoint personnel of the Huntley Fire Protection District to assist in enforcing this Ordinance. Such appointments shall include, but be not limited to a Fire Marshal, and as many inspectors, investigators, and public safety educators as may be needed. For the purposes of this Code, the Fire Marshal is the same as the Code Official.

 

 

SECTION 104 – GENERAL AUTHORITY AND RESPONSIBILITIES

 

104.8 Modifications

Delete this section and insert the following:

 

The Chief of the Huntley Fire Protection District may grant a variance regarding any of the provisions of this Code upon application in writing by the owner or lessee of the building or structure, or their duly authorized agent, where there are practical difficulties in the way of carrying out the strict letter of this Code, provided that the spirit of the Ordinance codified in this chapter shall be observed, public safety secured, and substantial justice done. If the Fire Chief decides to grant a variance, he may place conditions thereon. The decision of the Fire Chief in either granting or denying the variance shall be in writing and entered in the records of the Huntley Fire Protection District. A signed copy of the Fire Chief’s decision shall be furnished to the applicant.

 

104.10.2 Reporting hazardous locations

Add as an additional section:

 

Any person discovering the evidence of spontaneous heating or other abnormal heating of any kind in any building, marine vessel, appliance, apparatus, tank, or open stack or pile, or any person upon discovering or being apprised of an uncontrolled hazardous gas leak or hazardous material or flammable and/or combustible liquid spill, shall immediately notify the Huntley Fire Protection District.

 

 

SECTION 105 - PERMITS

 

105.1.1 Permits Required

Delete this section and insert the following:           

 

Permits shall be obtained from the Huntley Fire Protection District as required in other sections of this Code. Permits shall be valid only for the calendar year they were issued for, or until the expiration date on the permit for temporary permits. A new permit along with the fee set forth in Section 105.8 shall be required each calendar year. Issued permits shall be kept on the premises designated therein at all times and shall be readily available for inspection by the Code Official.

            Exception – Intergovernmental Agreement with Municipal Jurisdiction.

 

105.6 Required Operational permits

Delete this section and insert the following:

 

Permits will be required for Fireworks displays, carnivals, circuses, use of temporary membrane structures, and for installation of outdoor fireplaces.

 

105.8 Operational Permit Fees (Annual Permit Fee or Event)

Add as an additional section:

 

The following fees are established for any operational permits required by this Code, and shall be submitted along with the permit application. 

 

 

Fee Schedule –

Administrative Operation Fees

Fireworks permit and inspection                                                $  50.00  minimum

Carnival / Circus inspection                                                       $100.00 minimum

Temporary membrane structures, tents, canopies                       $   50.00 minimum

Outdoor Fireplaces                                                                   $   50.00 minimum

  

A fee of $ 60.00 per hour per inspector shall be required when, in the discretion of the Fire Chief a permit, review and /or inspection is required and it has not been specifically addressed in this ordinance.  The hourly fee is charged in 1 hour increments with a minimum of a full hour charge for any portion thereof.  The time charged starts when the inspector leaves his assigned station or is diverted from his assigned duties.  This fee shall also apply to building walk through inspections.

 

Add as additional sections:

 

105.9 The right of site development and construction plan review

 

Each applicant for a building permit involving new construction, additions and/or alterations, subdivision improvements, Planned Unit Developments (P.U.D.’s), fire detection/suppression systems or any other item that will affect the Huntley Fire Protection District operation, shall submit to the Code Official for review and approval, three (3) sets of all required plans, documents and a complete description of work to be performed. Only site development and sprinkler system plans and documents will be required for all single-family residences. The Code Official shall, within ten (10) days, examine said plans and documents to determine compliance with the applicable codes, standards, ordinances and good fire safety practices. If said plans are approved, the Code Official shall endorse said plans accordingly, and deliver said plans to the Building Official. If said plans are found to be unsatisfactory, then said plans shall be returned to the applicant with a memorandum listing the specified deficiencies found. A copy of the list of deficiencies shall be delivered to the Building Official with a recommendation to reject said plans until corrected.

            Exception – Intergovernmental Agreement with Municipal Jurisdiction.

 

105.9.1 Plan review and site inspection fee schedule

 

Each applicant shall pay the following plan review and site inspection fees for review and site inspection by the Huntley Fire Protection District Fire Prevention Bureau.  No part of said fees shall be refundable. Plan review fees shall include re-reviews, along with preliminary site visits up to a total of three (3) inspections for the each category.

 

Site Plan – New development                                                                                    $150.00

New construction – Commercial / Retail                                                                                         

            Life Safety Review:                                                                   $ .10/square foot

 

New Construction – Single and multiple family                                $ 100/each unit

 

Automatic fire-extinguishing systems

            NFPA  13 R or 13D (Single family residences):             $200.00 Minimum

            Small-scale tenant remodel of sprinkler system:              $100.00 Minimum

           

 

NOTE:  In addition to the review fees listed, the applicant shall pay, prior to the issuance of any permit, the actual costs and expenses incurred by Huntley Fire Protection District for extraordinary reviews of plans or specifications beyond the review customarily involved in the usual course of such plan reviews. Such costs and expenses shall include actual review fees by consultants or outside contractors or time spent by Huntley Fire Protection District staff. Huntley Fire Protection District staff time shall be billed at an hourly rate to be determined by the Fire Chief or designee.      

            Exception – Intergovernmental Agreement with Municipal Jurisdiction.

 

 

 

 

 105.9.2 New development donations/impact

 

The Huntley Fire Protection District has established the following fees for dwelling unit constructions within their jurisdiction for compensation of equipment, facilities and personnel in addition to all other fees depicted through the ordinances provided elsewhere. The developer contribution fee per dwelling unit is as follows:

 

1.       All Dwelling Units -   $600.00 each

 

Any future expansion or increase in density, following approval of the preliminary plat, will be subject to the contribution payment schedule. Payment will be due at a time agreed upon by both parties prior to the issuance of any building permits.

 

Exception – Intergovernmental Agreement with Municipal Jurisdiction.

 

SECTION 108 - BOARD OF APPEALS

 

108.1 Board of appeals established

Delete this section and insert the following:

 

Whenever the Code Official shall disapprove an application, or refuse to grant permission or when it is claimed that the true intent and meaning of the Ordinance have been misconstrued or wrongly interpreted, the applicant or person affected may appeal the decision of the Code Official to the Chief of the Huntley Fire Protection District by written notice filed in the Huntley Fire Protection District Chief’s office within five (5) days from the date of the decision being appealed. The said Chief shall render a decision on said appeal within fifteen (15) days of said notice. If the Chiefs decision does not resolve the matter, the applicant or person affected may appeal to the Huntley Fire Protection Districts Board of Trustees by written notice filed in the Huntley Fire Protection Districts administrative offices within ten (10) days of the Chiefs decision. The Board of Trustees shall call a hearing on said appeal within forty five (45) days of said notice of appeal filing, and shall render a decision within (10) days after completing such hearings. Nothing herein shall restrict the Code Official from seeking immediate enforcement of the regulation of this Ordinance in Court where the hazard involved requires such action.

 

108.1.1 Court of jurisdiction

 

Any person aggrieved by a decision of the Board, may apply to the appropriate Court of Jurisdiction. Application for review shall be made to the proper court within fifteen (15) days after the filing of the Board’s decision in the office of the Secretary of the Board.

 

 

 

 

 

SECTION 109 - VIOLATIONS

 

109.3 Violation Penalties

Delete this section and insert the following:

 

Any person, firm, or corporation who shall violate any provision of this Code or shall fail to comply with any of the requirements thereof or shall erect, construct, alter or repair a building or structure in violation of an approved plan or directive from the Code Official, or of a permit or Certificate of Occupancy issued under the provisions of this Code, shall be guilty of a misdemeanor, punishable by a fine of not less than $150.00 and not more than $750.00 per offense, or by imprisonment not exceeding 180 days, or both such fine and imprisonment.  Each day the violation continues after due notice has been served shall be deemed a separate offense.

 

111.4 Failure to comply.

Insert the following amounts in their appropriate designated place.

...not less than ($150.00) dollars or more than ($750.00) dollars.

 

CHAPTER 3 - GENERAL PRECAUTIONS AGAINST FIRE

 

 

SECTION 301 – GENERAL

 

301.3 Items not specifically covered

Add as an additional section:

 

Whenever or wherever a condition is found in any building, lot, or premises, that in the opinion of the Code Official is not specifically covered by the provisions of this Chapter, but that requires correction or removal for the protection of the occupants or the public, the Code Official shall order such conditions be corrected or removed and the owner or occupant of such buildings, lots, or premises shall comply with such orders.

  

SECTION 304 – COMBUSTIBLE WASTE MATERIALS

 

304.1.4 Sweeping Compounds

Add as additional section:

 

Only approved water solutions or detergent floor sweeping compounds, and grease absorbents shall be used for cleaning floors. The use of sawdust or similar combustible products on combustible or flammable liquids spilled from machinery or processed on any floor is prohibited.

 

 

 

 

 

SECTION 305 – IGNITION SOURCES

 

Add as additional sections:

 

305.5 Portable Heaters

Portable heaters shall be designed and located so that they cannot be easily overturned, and heaters shall be designed to shut off if overturned. The Code Official may prohibit the use of portable heaters in occupancies or situations in which such use or operation would present an undue danger to the life or property of others. Any portable heaters or devices used to provide heat shall be listed by an approved agency as accepted by the Code Official.

 

305.6 Heating and lighting apparatus

Proper clearance (a minimum of 36 inches) shall be maintained between lighting and heat producing equipment and combustibles so that continuous operation at full capacity will not increase the temperature of the surrounding combustibles to their flash point or ignition temperature.

 

SECTION 307 – OPEN BURNING

 

307.3.2 Recreational Fires

 insert  the following:

 

 Exception – Intergovernmental agreements with Municipal Jurisdictions

 

307.5 Stationary Outdoor Fireplaces

Add as additional section:

 

Stationary outdoor fireplaces require a permit for construction and use and must be approved by the Fire Code Official.

 

 307.6 Spread of fire

Add as addition section:

 

No person shall knowingly permit any fire to spread so as to endanger the life or property of another or use or operate any device which may be a source of ignition, unless proper removal of flammable material surrounding the operation is accomplished, or such other reasonable precautions are taken to ensure against the starting or spreading of unfriendly fires.

 

SECTION 308 – OPEN FLAMES

 

308.3.1    Open Flame Cooking Devices

Revise exception 1 to:

 

1.  One and Two family units and town home type complexes with six (6) units or less as determined by the Fire Official.

 

308.6 – Portable outdoor fireplaces

Add as additional section:

 

Portable outdoor fireplaces approved by the code official, shall be used only on noncombustible surfaces and shall be operated no closer than ten (10) feet from any structure or property line. Fuel for an outdoor fireplace shall consist of only seasoned, dry firewood or product manufactured or produced for such use and shall be ignited in an approved manner. All approved fuel sources intended for use shall be placed in such a manner as to not provide for independent ignition.

 

Section 316  Roof Coverings

Add as additional section:

 

Wood shingles are not permitted for use in the roofing or re-roofing of any building.      

 

 

CHAPTER 5 - FIRE SERVICE FEATURES

 

 

SECTION 503 - FIRE APPARATUS ACCESS ROADS

 

503.1.1 Buildings and facilities

Delete exception 1

 

503.1.4 Approval

Add as additional section:

The location of the fire apparatus roads or fire lanes shall be reviewed and approved by the Huntley Fire Protection District.

 

503.2.3 Surfaces

Delete this section and insert the following:

 

Fire apparatus access roads or fire lanes shall have a solid surface capable of supporting the appropriate fire apparatus as approved by the Fire Code Official.. Fire apparatus roads shall be pitched in such a manner as to allow the runoff of water and eliminate the potential of standing water. It shall be the responsibility of the property owner to maintain the surface in a usable condition at all times, including the removal of snow.

 

503.2.4

Add

The required turning radius of fire apparatus access roads shall be a minimum of 60 feet (outside radius).

 

SECTION 506 - KEY BOXES

Delete this section and insert the following:

 

506.1 When required

When access to, or within a structure, or an area unduly difficulty because of secured openings, or to gain access to fire protection controls, and where immediate access is necessary for life saving or fire fighting purposes, the Code Official shall require a minimum of one key lock box to be installed at a height not to exceed six (6) feet, in an accessible location. All buildings with automatic fire alarm systems and/or automatic fire suppression sprinkler systems shall have installed an approved key lock box for access by the Huntley Fire Protection District. The key lock box shall be of an approved type and shall contain keys to gain access as required by the Code Official.

 

506.2 Key lock box maintenance

Delete this section and insert the following:

 

The operator of the building shall immediately notify the Code Official and provide the new key when a lock is changed or re-keyed. The key to such lock shall be secured in the key lock box. The users shall be responsible for the proper installation and maintenance of such key lock boxes, at their expense, and shall agree to indemnify and hold harmless the Huntley Fire Protection District, and their officers, employees and agents from any liability with respect to such key lock boxes.

 

SECTION 508 - FIRE PROTECTION WATER SUPPLIES

 

508.1 Required water supply

Add as additional requirements to this section:

 

508.1.1 General

 

All water distribution facilities including piping, fittings, hydrants, valves, devices, well pumps, and other needful appurtenances shall be subject to approval of the Code Official and shall be installed according to the standards herein adopted. A water supply system shall be capable of supplying the hydrants prior to the construction of structures. It shall be unlawful to erect, alter, use or occupy any structure that has been deemed to have inadequate water supply.

 

508.1.2 Water supply demand changes

 

Area water supplies shall be studied whenever additional demands will be placed on the water supply by new construction, change in use, or changes in hazard or contents. Standard fire flow calculation methods will be used to make determinations. Upon determination by the Code Official that inadequate water supplies exist, the Code Official shall reject any applicable plans and provide the property owner, the water utility, and the Building Official with a memorandum listing said deficiencies.

 

508.3 Fire flow

Add as additional requirement to this section:

 

508.3.1 Minimum flow requirements

 

Each fire hydrant shall be provided with an adequate water supply so as to develop a minimum individual supply of not less than one thousand (1,000) gallons per minute flow with not less than 20 pounds per square inch residual pressure or as indicated in Appendix B as determined by the Fire Code Official.

 

508.5 Fire hydrant systems

 

508.5.1 Where required

Delete this section and insert the following:

 

The maximum hydrant spacing shall not exceed three hundred (300) feet from the furthest point of any building or structure as measured by an approved access route around the exterior of the facility or building unless otherwise approved by the Code Official. Where the configuration of lots, distances between buildings and lot lines or public utility easements, accessibility to buildings for fire suppression requirements dictate, the Code Official shall increase or decrease hydrant spacing and appropriate supply mains as deemed necessary.

 

508.5.1.1 General

 

Additional fire hydrants shall be located within one hundred fifty (150) feet of any Fire Department Connection (FDC). Hydrants shall not be installed on water main less than six (6) inches in diameter. Dead end water mains shall not to exceed one hundred (100) feet of six (6) inch pipe and six hundred (600) feet of eight (8) inch pipe. It is recommended that a looped water main system with a minimum pipe diameter of eight (8) inches be required for each structure or group of structures.

 

Exception: Intergovernmental agreements with municipalities

 

508.5.1.2

 

All steamer ports shall be installed facing the right of way or as otherwise approved by the Huntley Fire Protection District.

 

Fire service main shall be looped when there is a dead end greater than 300 feet.

 

All site developments shall be served by a looped municipal water system where hydrants are planned.

 

The fire service main (lead-in) shall be a minimum of six (6) inches in diameter but not less than the smallest riser.

 

All fire service mains shall be looped around the building when a building exceeds 52,000 square feet in area or is classified as an unlimited area building.

 

508.5.7    Identification

Add as an additional requirement to this section:

 

1.         All fire hydrants (public or private) shall be marked with a hydrant flag that is approved by the Code Official.

2.         All private hydrants shall be painted yellow in color by the manufacturer prior to installation.  The Fire Code Official shall require color-coding of supply size and the provider / installer shall paint as required per NFPA 291 requirements.

 

Exception:  Intergovernmental agreements

  

508.5.7 Identification

Add as additional requirements to this section:

 

  1. All fire hydrants public or private shall be marked with a hydrant flag that is approved by the Code Official.

2.   All private hydrants shall be painted yellow in color by the manufacturer or prior to installation. The Fire Code Official shall require color-coding of supply size and the provider / installer shall paint as required.

 

508.5.8 Apartment and cluster type housing

 

In areas where apartment buildings, town/row houses, condominium buildings, or other types of cluster-type housing are located, the area along the roadway within seven and one-half feet on either side of the fire hydrant shall be designated as "NO PARKING" and either the curb shall be painted yellow or "NO PARKING" signs shall be installed (or both).

  

SECTION 511 - ELEVATORS

 

511.1 When Required

Add as additional requirements to this section:

 

Elevator service shall be provided in all buildings and structures three (3) stories or greater in height, measured from the lowest level of fire department vehicle access. 

 

Exception: One and two-family residences, unless covered elsewhere in this Code.

 

 

 

 

511.2 – Elevator car requirements

 

Elevator cars are to accommodate the ambulance stretcher. In the buildings two stories in height or more, at least one elevator shall be of such a size and arrangement to accommodate a 28-inch by 84-inch ambulance stretcher in the horizontal, open position and shall be identified by the international symbol for emergency medical services (Star of Life). The symbol shall not be less than 3 inches high and shall be placed inside on both sides of the hoist way doorframe. The inside hand rail shall be set at the maximum thirty six (36) inch height allowed under ADA standards to better accommodate the stretcher. The cab size is to be minimum a 5’ x 7’ platform and minimum 2500 lb capacity with a 42” side slide door.

 

 

CHAPTER 6 - BUILDING SERVICES AND SYSTEMS

 

 

SECTION 610 - COMMERCIAL KITCHEN HOODS

 

Add as additional sections:

 

610.1.2 Existing kitchen hood fire suppression systems

 

Each existing required commercial or other occupancy kitchen exhaust hood and duct system shall be protected with an approved wet chemical fire suppression system installed and maintained per NFPA 17, and UL 300 Standard. Every required automatic fire suppression system, when activated shall transmit a fire alarm signal to the Huntley Fire Protection District main dispatch center via an approved fire alarm system.

 

610.8 Maintenance

 

Commercial kitchen exhaust systems shall be cleaned to remove deposits of residue and grease in the system at intervals specified in the cleaning schedule required to be submitted in accordance with the mechanical code listed in Chapter 45.  Thorough cleaning of ducts, hoods and fans shall require scraping, brushing or other positive cleaning methods.

 

610.8.1 Cleaning Schedule

 

            Where a cleaning schedule is not on file, the Code Official shall require a schedule to be submitted, indicating the method of cleaning and the time intervals between cleanings.

 

    

 

 

 

    

CHAPTER 9- FIRE PROTECTION SYSTEMS

 

 

SECTION 903 – FIRE PROTECTION SYSTEMS

 

903.1 Alternative protection

Delete this section and insert the following:

 

Alternative automatic fire extinguishing systems complying with Section 904 may be permitted in lieu of automatic sprinkler protection where recognized by the applicable standard and approved by the Code Official.

 

903.2 Where required

Delete this section and insert the following:

 

Approved automatic sprinkler systems in new buildings and structures shall be provided in all Use Groups described in this Code. Automatic sprinkler systems must be installed in accordance with applicable NFPA standards, manufacturer’s recommendations, UL listings, and good fire safety practices. Automatic sprinkler systems must be maintained in full operating condition at all times. Automatic sprinkler systems shall be provided in all new residential Use Groups including town homes/multi-family dwellings, and one and two family dwellings, which are adopted by this Code. All new single-family dwellings shall have automatic fire sprinklers installed throughout per NFPA 13R or 13D.  All new town homes shall have automatic fire sprinklers installed throughout per NFPA 13R or 13D. All new attached garages shall have automatic sprinklers installed utilizing dry sidewall or dry pendant sprinklers approved for that use.

 

This section of the code is to become effective May1, 2005.

 

Exceptions:  Real estate sales and construction trailers utilized during the development of property when approved by the code official, agriculture storage buildings not used by the general public.

 

903.2.1 Through 903.2.3.1 Where required

Delete these sections in their entirety

 

903.2.6 Through 903.2.12.3 Where required

Delete these sections in their entirety

 

903.3.1.1.1 Exempt locations

Delete this section in its entirety

 

 

 

 

 

903.4.1 Signals

Delete this section and insert the following:

 

All automatic fire suppression systems required for occupancies in Use Groups A, B, E, F, H, I, M, S, R-1, R-2, R-3 and R-4, shall be supervised by directly connecting to the main dispatch center for the Huntley Fire Protection District with NFPA 72 and their respective listing by an approved agency.

Note – Not intended for single-family detached dwelling units.

 

903.4.2 Alarms

Delete this section and insert the following:

 

Approved audible devices shall be connected to every automatic sprinkler system. Such sprinkler water flow devices shall be activated by a water flow equivalent to the flow of a single sprinkler of the smallest orifice size installed in the system. All water flow devices shall activate alarm notification devices in compliance with NFPA 13 and 72.

 

There shall be a white horn/strobe unit installed in an approved weatherproof housing above each fire department connection for each automatic sprinkler system 

 

Remote fire alarm detection system station monitoring connection is required to go directly to the main dispatch center of the Huntley Fire Protection District. The method of connection must be of a type approved by the Fire Code Official.

 

Note – Not intended for single-family detached dwelling units.

 

 903.4.3 Floor control valves

Delete this section and insert the following:

 

In multi story buildings, approved floor control valves with water flow switches shall be provided for each floor. In large multi tenant buildings, a smoke detection system approved by the Fire Code Official is required per NFPA 72.

 

Add as additional sections:

 

903.4.5 Sprinkler control valves

 

All new and existing sprinkler control valves shall be equipped with electronic supervision (tamper switches) in accordance with NFPA 72. All new tamper switches installed shall have the capability to self-restore.

.

Note – Not intended for single-family detached dwelling units.

 

 

 

 

903.6 Remodels of existing buildings

add:

Existing buildings or structures that are remodeled, repaired, either voluntary or by involuntary act and that meet any of the criteria listed below, shall provide fire protection for the structure as detailed in 903.2:

 

  1. If alteration costs 50% or more of the reproduction cost of the building or structure, the entire building or structure shall comply with the requirements of the construction as defined in this code. For the purpose of calculating percentages of reproduction cost, the alteration shall be construed as the total actual combined cost of all alterations made within any period of 30 months.
  2. For the entire structure or building where there are any additions or alterations increasing the existing fire area of the building.
  3. A project that results in an increase or decrease in the total number of tenant spaces within the building or structure.
  4. A project that entails a change in Use Group for any part of the building.
  5. A project conducted on a building that by reason of its construction methods, existing or proposed provide a hazard to its occupants or emergency response personnel in the event of a fire or emergency response incident, as determined by the Fire Chief or their designee.

 

Exception: One and two family detached dwellings.

 

Fire protection for additions that increase the existing floor area of a building or structure by 25% or less shall be as follows:

 

a.       Provide fire protection for the entire building or structure as detailed in 903.2 or

b.      Provide a UL listed three-hour fire separation assembly between the existing building and the new addition. Provide fire protection for the new addition as detailed in 903.2.

 

Exception: One or two family detached dwellings.

 

903.7 Hydraulic calculations

 

Provide a minimum 10% or 5 psi minimum safety factor in the fire protection system hydraulic calculation. The system demand shall be 5 psi minimum below the seasonal low water flow test supply. The safety factor will allow for low pressures in the water supply. By each hydraulic calculated area, on each drawing, provide a copy of the hydraulic nameplate. This will make it easier to check the hydraulics of the sprinkler system for future building or storage changes.

 

903.8 Appendices of NFPA standards

 

Each appendix of the NFPA standards are to be considered as part of each standard and are considered a “shall” requirement and not “should” information. This will require sprinkler system installations to be installed per NFPA requirements and NFPA recommendations for good engineering practices and installations.

 

903.9 Fire pump test header

Provide an OS&Y control valve on all fire pump test headers. Provide an outside test header on fire pump installations.

 

Section 903.8 - Sprinkler System safety factor

Provide a minimum 10% or 5 psi minimum safety factor in fire protection system hydraulic calculation.  The system demand shall be 5-psi minimum below the seasonal low water flow test supply.

 

Section 903.9 - Sprinkler System nameplate:

By each hydraulically calculated area, on each drawing, provide a copy of the hydraulic nameplate.

  

903.10 Sprinkler room access

 

Provide an outside or inside access door at ground level to the sprinkler riser valve room and/or the fire pump room.

 

903.11 Sprinkler room fire separation

 

Provide a minimum one (1) hour fire separation for the sprinkler riser valve room and/or the fire pump room.

 

903.12 Check valves

 

Provide a check valve in each sprinkler riser. This will prevent each sprinkler system riser from going into alarm.

 

903.13 Sprinklers

 

Office, assembly and residential buildings shall be provided with residential and/or quick response sprinklers.

 

903. 14 Fire hose valves – Warehouse storage areas

 

In all warehouse storage areas, where storage exceeds twelve (12) feet high, provide inside 2 ½” fire hose valves with 1 ½” reducer to a 1 ½” connection. Locate the valves at each door entrance to the warehouse and/or storage area. Provide additional 2 ½” fire hose valves so that no portion of the warehouse and/or storage area is more than 120’ maximum travel distance to a fire hose valve. Show the location of all obstructions and/or racks on the drawing.

 

Fire hose valves system piping shall be:

 

  1. A separate riser piping system.
  2. Hydraulically calculated for a minimum of 250 gpm at 75 psi to the most hydraulically remote fire hose valve.
  3. Where system pressures exceed 100 psi, provide Potter (or equally approved) reduced pressure field adjustable type valves.

 

 Section 904 – Alternative automatic fire-extinguishing systems

 

904.3.4.1 Kitchen hood suppression systems

Add as an additional section:

 

Kitchen hood suppression systems shall be connected to the building fire alarm system available.

 

SECTION 905 – STANDPIPE SYSTEMS

 

905.3 Required installations

Add the following paragraph to section 905.3:

 

All required standpipe systems shall be supplied by a separate riser. The supply riser shall be hydraulically designed to supply 2 ½” hose drops. The riser system shall be equipped with a separate control valve and flow switch. The standpipe shall be a 2 ½” gated connection with a 1 ½” reducer and the Code Official shall approve all locations. All standpipe and sprinkler risers shall have separate control valves and flow switches per floor.

 

905.3.1 Building height

Delete this section and insert the following:

 

Class III standpipe systems shall be installed throughout all buildings or structures more than two (2) stories in height.

 

Exceptions:

  1. Class I stand pipes are allowed in buildings equipped with an automatic sprinkler system in accordance with Section 903.1.1 or 903.1.2.
  2. Class I manual standpipes are allowed in open parking garages where the highest floor is located not more than 150 feet above the lowest level of the fire department vehicle access Class I manual dry standpipes are allowed in open parking garages subject to freezing.
  3. Class I standpipes are allowed in basements equipped throughout with an automatic sprinkler system.

 

 

Add as additional sections:

 

905.12 Piping design

 

The riser piping, supply piping and the water service piping shall be sized to maintain a residual pressure of at least 65 psi (448kPa) at the topmost outlet of each riser while flowing the minimum quantities of water specified in Section 905.11.1 and 905.11.2. The piping size shall be based on the capacity of the automatic water supply system or, where as automatic water supply is neither required nor provided to maintain the residual pressure of 65 psi, the pipe size shall be on a pressure of 150 psi available at the fire department connection.

 

Exception:  The residual pressure of 65 psi is not required in buildings equipped throughout with an automatic sprinkler system in accordance with Section 903.3 and where the highest floor level is not more than 150 feet above the lowest level of fire department vehicle access.

 

Exception:  One and two family dwellings

 

905.12.1 Riser sizing

 

The riser size shall be based on the hydraulic calculations for a minimum flow of 500 gallons per (gpm) (378 L/min.).

 

Exceptions:

 

  1. Where only 1 ½” valves are provided, the riser(s) shall be sized to provide a minimum flow of 100 gpm (378 L/min).
  2. In buildings where limited area sprinkler systems are supplied with water from a common standpipe riser, the riser shall be sized to satisfy total demand.
  3. For occupancies Use Group B, I, R1, or R2 in buildings that are equipped throughout with an automatic sprinkler system in accordance with Section 903.3, each riser shall be sized for a minimum flow of 250 gpm (945 L/min.).
  4. Risers that are sized in accordance with the pipe schedule requirements of NFPA 14 listed in Chapter 35 are not subject to this requirement.

 

SECTION 907 - FIRE ALARM AND DETECTION SYSTEMS

 

907.1.2 Equipment

Add the following language to the existing section:

 

New fire alarm control panels shall be addressable unless otherwise approved by the Code Official. The equipment shall be capable of having the audio signal silence without resetting the fire alarm control panel. All fire alarm control panels shall have an approved method of placing the system in trouble mode at the location of the alarm panel.

  

907.21.1 – False Fire Alarm :Definition

 

False fire alarm: Any alarm signal which indicates the existence of an emergency situation, when in fact no such emergency exists, and shall include any alarm signal generated by any fire protection system by whatever means

 

907.21.3 False fire alarm service charge

 

Exception – Intergovernmental Agreement with Municipal Jurisdiction.

 

For false fire alarms, an alarm user shall be charged a service charge of $300.00 for each false alarm in excess of three (3) in any calendar year. All false fire alarm service charges shall be remitted to the Huntley Fire Protection District by the alarm user upon receipt of the statement for such service charge.

 

907.21.6 Liability

 

The Huntley Fire Protection District assumes no liability for:

 

  1. Any defects in the operation of an alarm system.
  2. Any failure or neglect to respond appropriately upon receipt of an alarm.
  3. Any failure or neglect of any person in connection with the installation, operation, or maintenance of any alarm system.
  4. The transmission of alarm signals, prerecorded alarm messages, or the relaying of such signals and messages.

 

 907.21.8 Penalties

 

Any person who violates any of the provisions of this Article shall be subject to a fine of not more than $500.00 for each violation. Such fines shall be in addition to any other fee or charge authorized pursuant to the terms of the ordinance codified in this chapter.

 

CHAPTER 33

EXPLOSIVES AND FIREWORKS

 

 SECTION 3302 - DEFINITIONS

Add as additional section:

 

3302.1  FIREWORKS : Definition

 

The following words and terms shall, for the purpose of this Chapter and as stated elsewhere in this Code, have the meanings shown herein.

 

Fireworks: The term "fireworks" shall mean and include any explosive composition, or any substance or combination of substances, or article prepared for the purpose of producing a visible or audible effect of a temporary exhibition in nature by explosion, combustion, deflagration or detonation, and shall include blank cartridges, toy cannons, in which explosives are used, the type of balloons which require fire underneath to propel the same, firecrackers, torpedoes, sky-rockets, Roman candles, bombs, or other fireworks of like construction and any fireworks containing any explosive compound, or any tablets or other device containing any explosive substance, or containing combustible substances producing visual effects, provided, however, that the term "fireworks" shall not include trick noise makers known as "party poppers", "booby traps",  and "snappers"; toy pistols, toy canes, toy guns, or other devices in which paper or plastic caps containing twenty-five hundredths of grains or less of explosive compound are used, providing they are so constructed that the hand cannot come in contact with the cap when in place for the explosion; and toy pistol paper or plastic caps which contain less than twenty hundredths grains of explosive mixture.

 

Note:    Devices such as sparklers, snake or glow worm pellets, trick matches, etc. that require an open flame, such as a match or lighter, to ignite are not permitted.

SECTION 3304 - EXPLOSIVE MATERIALS STORAGE AND HANDLING

Delete this section and insert the following:

 

3304.1 – Explosive materials storage and handling

 

The storage of explosive materials is prohibited unless otherwise approved by the Huntley Fire Protection District.

SECTION 3308 - FIREWORKS DISPLAY

 

3308.2 Permit application

Delete this section and insert the following:

 

A permit shall be required for the possession, display or discharge of fireworks or pyrotechnical displays. The permit application shall include the applicant’s name, address, and age; the date and place of the proposed discharge of fireworks or pyrotechnical display; the nature and quantities of fireworks to be discharged or displayed; and the applicant’s experience, if any, in discharge of fireworks or pyrotechnical displays. Also included shall be plans for the display, inspections of the display site, and demonstrations of the display operation.  Such permit shall be applied for a minimum of fifteen (15) days prior to the proposed date of display. 

 

Upon receipt of the application, the Code Official, or designee, shall inspect the location of the proposed discharge of fireworks or pyrotechnical display. If, in the judgment of the Code Official, or designee it would not be hazardous to any property or persons to allow such discharge of fireworks or pyrotechnical displays, given the resources of the Fire Department available for the requested date, the Code Official shall approve the application and issue a permit for the discharge of fireworks or pyrotechnical display.  Fees in accordance with Section 105.8 shall apply. 

 

A permit granted hereunder shall not be transferable, nor shall any such permit be extended beyond the dates set out therein.

 

Section 3308.11 Fireworks / Retail Display and Sale,

Delete present section and add:

A person shall not possess, manufacture, store, offer or expose for sale, sell at retail or discharge any fireworks within the Huntley Fire Protection District with the exception of approved supervised displays of fireworks in accordance with section 3308 of this code.

 

Add as additional section:

 

SECTION 3309 - VIOLATIONS

 

Section 3309.1 General

A person shall not possess, manufacture, store, offer or expose for sale, sell at retail or discharge any fireworks within the Huntley Fire Protection District.

 

Exception: Where approved for the supervised display of fireworks in accordance with Section 3308 of this Code.

 

Section 3309.2 Bond for display

 

The permit holder shall furnish a bond in an amount approved by the code official for the payment of all potential damage caused either to the person or property due to the permitted display, and arising from any acts of the permit holder or agent of the permit holder. In lieu of a bond, the permit holder may provide a certificate of insurance, in an amount acceptable to the Code Official as an additional insured and execute an agreement holding the Huntley Fire Protection District harmless from any damage to persons or property caused by the permitted display.

 

Section 3309.3 Fines for violations

 

Any person, firm, partnership, association or corporation found violating any of the provisions of this chapter shall be fined not less than one hundred and fifty dollars ($150.00), but not more than seven hundred and fifty dollars ($750.00).

 

 

 

 

 

 

 

CHAPTER 45

REFERENCED STANDARDS

 

 

Add the following standards or change to the edition indicated:

 

NFPA 11 – 2002         NFPA 11A – 2002      NFPA 12 – 2003         NFPA 12A – 1998

 

NFPA 13 – 2002         NFPA 13D – 2002      NFPA 13R – 2002      NFPA 14 – 2003

 

NFPA 15 – 2003         NFPA 16 – 2001         NFPA 17 – 2002         NFPA 17A – 2002

 

NFPA 20 – 1999         NFPA 22 – 1998         NFPA 25 – 2002         NFPA 30 – 2003

 

NFPA 30A – 2003      NFPA 30B – 2002      NFPA 32 – 2003         NFPA 33 – 2003

 

NFPA 34 – 2003         NFPA 40 – 1997         NFPA 61 – 2002         NFPA 70 – 2002

 

NFPA 72 – 2002         NFPA 80 – 1999         NFPA 96 – 2001         NFPA 99 – 2002

 

NFPA 110 – 2002       NFPA 111 – 2001       NFPA 204A – 2002

 

NFPA 252 – 1999       NFPA 253 – 2003       NFPA 257 – 2003       NFPA 265 – 2002

 

NFPA 409 – 2001       NFPA 418 – 2001       NFPA 654 – 2003       NFPA 655 – 2001

 

NFPA 664 – 2002       NFPA 701 – 1999       NFPA 704 – 1996       NFPA 1142 – 2001

 

NFPA 1144 – 2002     NFPA 2001 – 2003     NFPA 291

 

  

Appendix A

 

– is hereby deleted. Reference to Section 108 provides appropriate language.

  

Appendix B

Is hereby adopted to the text of the publication and is part of the adoption ordinance as referenced in Section 508.31.

                                                              

Appendix C

Is hereby deleted from the text of the publication and not part of this ordinance

  

Appendix D

Is hereby adopted to the text of the publication with exceptions and additions noted in Section 503 and is part of this adoption ordinance

 

Appendix E,  Appendix F, Appendix G

 

Is hereby adopted to the text of the publication and is part of the adoption ordinance.